Abstract
Non-azeotropic refrigerant mixtures (NARMs) are investigated for a two-temperature level heat exchange process found in a domestic refrigerator-freezer. Ideal (constant air temperature) heat exchange processes are assumed. The results allow the effects of intercooling between the evaporator refrigerant stream and the condenser outlet stream to be examined in a systematic manner. For the conditions studied, an idealized NARM system will have a limiting coefficient of performance (COP) that is less than that of the best performing pure refrigerant component. However, for non-ideal heat exchange processes (gliding air temperature), the NARM-based system can have a higher limiting COP than a system running on either pure NARM component. Intercooling significantly affects the COP of NARM-based systems; however, depending on the location of 'pinch points' in the heat exchangers, only one intercooling heat exchanger may be needed to obtain a NARM's maximum refrigerator COP. The results are presented for mixtures of R22-R142b, R22-R123 and R32-R142b.
Original language | English (US) |
---|---|
Pages (from-to) | 237-242 |
Number of pages | 6 |
Journal | International Journal of Refrigeration |
Volume | 13 |
Issue number | 4 |
DOIs | |
State | Published - Jul 1990 |
Externally published | Yes |
Keywords
- domestic refrigerator-freezers
- non-azeotropic refrigerant mixtures
- thermodynamic performance