Heat rejection from R744 flow under uniform temperature cooling in a horizontal smooth tube around the critical point

Chieko Kondou, Pega Hrnjak

Research output: Contribution to journalArticlepeer-review

Abstract

Heat rejection from CO2 flow near the critical point, where commercial refrigerators spend most of their operating hours, was investigated in this study. Experimental results on the heat transfer coefficient and pressure drop of mass flux from 100 to 240 kg m-2 s-1 at pressures from 5 to 7.5 MPa in a horizontal smooth tube of 6.1 mm inner diameter are provided and compared with correlations. The heat rejection process below critical pressure was categorized into superheat, two-phase, and subcool zones in which the bulk-mean temperature was superheated, saturated, and subcooled, respectively. The results indicated that the heat transfer coefficient in superheat zone is significantly higher than correlations proposed for single-phase turbulent flow, and the condensation was identified from the tube wall temperature below saturation temperature. This superheat zone accounts for a significant portion of the heat rejected in the subcritical cycle and affects on condenser sizing.

Original languageEnglish (US)
Pages (from-to)719-731
Number of pages13
JournalInternational Journal of Refrigeration
Volume34
Issue number3
DOIs
StatePublished - May 2011

Keywords

  • Carbon dioxide
  • Critical point
  • Heat transfer
  • Horizontal tube

ASJC Scopus subject areas

  • Building and Construction
  • Mechanical Engineering

Fingerprint

Dive into the research topics of 'Heat rejection from R744 flow under uniform temperature cooling in a horizontal smooth tube around the critical point'. Together they form a unique fingerprint.

Cite this