Abstract
In order to investigate the fouling of enhanced tubes, a continuous fouling test on eight enhanced tubes and one plain tube was conducted for 98 days, using a medium fouling potential water as the test water at a water velocity of ∼1.6 m/s. Four periods were defined for fouling development based on the test data in this work: introduction period, initial deposit period, rapid deposit period, and stabilization period. The rank of asymptotic fouling resistance of nine test tubes was as follows: Tubes 9 > 7 >6 > 5 > 1 >3 >4 >2 >8. The pressure drops of the nine tubes increased by 0.1 kPa to 1.32 kPa due to fouling deposit at the end of the fouling test. A fouling resistance prediction model was developed, which had a maximum error of 0.0645 for predicting the fouling resistance ratio.
Original language | English (US) |
---|---|
Pages (from-to) | 9-18 |
Number of pages | 10 |
Journal | International Journal of Refrigeration |
Volume | 104 |
DOIs | |
State | Published - Aug 2019 |
Keywords
- Enhanced tubes
- Fouling
- Fouling model
- Pressure drop
- Thermal resistance
ASJC Scopus subject areas
- Building and Construction
- Mechanical Engineering